Long-life protection for transmission towers

Coating system
| Layer | Material / system | DFT | Standard | |
|---|---|---|---|---|
| Primer | Epoxy primer for galvanised steel | 60 μm | ISO 12944-5 | |
| Intermediate | MIO epoxy intermediate | 80 μm | ISO 12944-5 | |
| Topcoat | Aliphatic polyurethane topcoat, UV stable | 60 μm | ISO 12944-5 | |
| Total system DFT | ≈ 200 μm | |||
Long-life overcoating on hot-dip galvanising; a dedicated epoxy primer improves adhesion to zinc and prevents saponification blistering.
High-voltage transmission towers in open terrain face wind-blown abrasion, UV, temperature swings and industrial atmospheres; aged galvanising needs long-life overcoating. Scope covered tower members, cross-arms and bolted joints.
A dedicated epoxy primer for galvanised steel improves adhesion, followed by micaceous iron epoxy intermediate and aliphatic polyurethane topcoat for UV and colour stability. Welds and damaged galvanising were locally repaired before full coating.
Dust, oil and loose zinc were removed before painting; temperature and humidity were controlled with adequate curing before rain. Each tower section was checked for DFT and appearance, with particular attention to bolts and crevices.
The build-ups above are typical systems compiled from ISO 12944 and the relevant product technical data sheets; film thicknesses are reference values for the service conditions stated. For any specific project, the design specification, tender documents and the manufacturer's latest PDS govern. Actual performance depends on surface preparation grade, ambient conditions during application and recoat intervals.